Convention Applied by the app elec.mount-height.defaults

Default mount heights for devices

The heights above finished floor the app starts each device at — 18" receptacles, 44" GFCI at a counter, 48" switches, 78" panel top — so the Chain tool can write the vertical.

The rule, as the app applies it
WhenThe app uses
Duplex receptacle, to center18 in AFF
GFCI receptacle at a counter44 in AFF
Single-pole switch48 in AFF
Panelboard, to the top78 in AFF
Exit sign90 in AFF
Data outlet18 in AFF
Thermostat48 in AFF
Source
NEC · 404.8(A), 240.24(A); ADA 308 reach range · read the public text
Editions checked
2020 · 2023
Used by
Chain tool Quick creator
Amendments

No state or local amendment to this rule is on file. Not on file means the model code as written — check your jurisdiction.

A working figure the trade uses and the app defaults to. Shops override these most.

No code tells you a receptacle goes at 18 inches. The NEC only caps how high a switch or a breaker handle may be (6 ft 7 in), and accessibility rules bound the reach range (15 to 48 inches for an unobstructed forward reach). Inside those, the trade has working figures, and the architect's elevations or the specification override them job by job.

What the app does with it

When you create a device on the Quick tab, its mount height is prefilled from this list and rides the counter; you can overwrite it before you Add or edit it later. The Chain tool then writes ceiling height minus mount height plus make-up as the vertical on every run it draws to that device. The panel figure is to the top of the can, which is what the homerun's vertical needs.

What it does not do

It does not read heights off the drawings. A device schedule that says 42 inches wins, and the counter is where you say so.

Cited by section, not reprinted: the code text belongs to its publisher. Company practice is not a rule here — it lives with your pricing. Updated Sep 9, 2026.