Convention Applied by the app elec.voltage-drop.k-constant

The K constant for voltage drop

The resistivity figure the estimator's single-phase voltage-drop formula uses — 12.9 for copper, 21.2 for aluminum, in ohm-circular-mils per foot.

The rule, as the app applies it
WhenThe app uses
copper conductors12.9 Ω·cmil/ft
aluminum conductors21.2 Ω·cmil/ft
Source
NEC · Chapter 9, Table 8 (as the trade rounds it) · read the public text
Editions checked
2017 · 2020 · 2023
Used by
Bid Check
Amendments

No state or local amendment to this rule is on file. Not on file means the model code as written — check your jurisdiction.

A working figure the trade uses and the app defaults to. Shops override these most.

Bid-day voltage drop is VD = 2 × K × I × L ÷ cmil for single phase: twice the one-way length, the current, the conductor's circular-mil area, and K — the resistance of a one-foot, one-circular-mil conductor at operating temperature. The trade's working figures are 12.9 for copper and 21.2 for aluminum; they are rounded from the resistance table in Chapter 9, not a value the Code prints as "K".

What the app does with it

Bid Check's voltage-drop row uses these two figures with the run length it measured (verticals included) and the circular-mil area of the smallest conductor on the circuit. The formula is single-phase; three-phase circuits would use √3 in place of 2, which the app does not yet do.

Cited by section, not reprinted: the code text belongs to its publisher. Company practice is not a rule here — it lives with your pricing. Updated Sep 9, 2026.