Standard Applied by the app hvac.duct.sheet-weight

Galvanized sheet weight by gauge

Pounds per square foot of galvanized steel sheet at each gauge — the basis of every duct weight the schedule reports.

The rule, as the app applies it
WhenThe app uses
26 gauge0.906 lb/ft²
24 gauge1.156 lb/ft²
22 gauge1.406 lb/ft²
20 gauge1.656 lb/ft²
18 gauge2.156 lb/ft²
Source
ASTM · A653 / A924, nominal galvanized sheet weight by gauge · read the public text
Editions checked
—
Used by
Duct Schedule
Amendments

No state or local amendment to this rule is on file. Not on file means the model code as written — check your jurisdiction.

An industry standard the trade builds to.

Duct is bought by the pound and bid by the pound. The weight of a run is its surface area — the perimeter of the size times the length — times the sheet weight at its gauge. These are the nominal galvanized figures the trade quotes; a specific coating class shifts them by a few percent.

What the app does with it

The Duct Schedule multiplies each run's perimeter in feet by its length and by this figure to report pounds per size, then adds fittings as pound-equivalents and the seam & waste percentage on top. Change a gauge and the pounds follow.

Cited by section, not reprinted: the code text belongs to its publisher. Company practice is not a rule here — it lives with your pricing. Updated Sep 9, 2026.